Determination of Corrosive Sulfide Dibenzyl Disulfide in Transformer Oil by High Performance Liquid Chromatography with Liquid-Liquid Microextraction |
|
View Full Text Download reader |
DOI: |
KeyWord:dibenzyl disulfide(DBDS) liquid-liquid microextraction high performance liquid chromatography(HPLC) transformer oil corrosive sulfide |
Author | Institution |
LI Hai-yan,LI Yin-shuang,YANG Zhen,FU Yu-cha |
1.College of Chemistry and Materials Science,South Central University for Nationalities;2.Key Laboratory of Analytical Chemistry for Environment and Biological Resources in Ethnic Districts,South Central University for Nationalities |
|
Hits: 1881 |
Download times: 493 |
Abstract: |
An analytical method was established for the determination of the main corrosive sulfide,dibenzyl disulfide(DBDS) in transformer insulating oil by high performance liquid chromatography(HPLC) with vortex assisted liquid-liquid microextraction(VA-LLME).Under the optimized conditions,the DBDS was quantified by external standard method and internal standard method with acetonitrile as extractant.Results showed that there were good linear relationship for DBDS in the concentration range of 0.1-600.0 mg/kg with correlation coefficients(r) more than 0.999.The limits of detection(LOD,S/N=3) were in the range of 6.9-7.1 μg/kg.The method was applied in the determination of target analytes in commercial transformer oil samples and aging oil samples.The recoveries were in the range of 95.0%-112% with relative standard deviations(RSD) not more than 2.3%.The method has the characteristics of high efficiency,high sensitivity and environmental friendliness,and has no significant difference with the GC-ECD method of IEC 62697 in USA and GC-MS method of GB/T 32508 in China.It also provides references for the standards revision of quantitative detection of corrosive sulfide DBDS in transformer oils in China. |
Close |
|
|
|